atrea_control
Ruby client for ATREA DUPLEX ventilation units with RD5 regulation, using the RD5 cloud portal. RD5-only support is intentional: this unofficial gem uses cloud HTTP/XML, not aMotion Cloud or Modbus TCP.
Login and end-to-end reads were verified against a live RD5 unit on 2026-10-25:
configuration discovery, fresh snapshots, getters/JSON and repeated refreshes
succeeded. A missing Sync=1 parameter in the unit-login request was corrected
after comparison with the current portal. Live writes and requested-value
read-back semantics remain unverified. See protocol evidence and limitations.
Installation
gem "atrea_control"Run bundle install, or install directly with gem install atrea_control.
Login and snapshots
Supply credentials through your application's environment. The library does not
load .env files automatically. Never log credentials or returned tokens.
require "atrea_control"
tokens = AtreaControl::Duplex::Login.user_tokens(
login: ENV.fetch("ATREA_USERNAME"),
password: ENV.fetch("ATREA_PASSWORD"),
unit_id: ENV.fetch("ATREA_UNIT_IDENT"),
timeout: 300,
poll_interval: 1,
open_timeout: 10,
read_timeout: 60
)
control = AtreaControl::Duplex::Unit.new(**tokens, time_zone: "Europe/Prague")
values = control.values
values[:current_power] # Numeric configured power value, not universally percent.
values[:current_mode] # Translated label; may describe a user input such as CO2.
control.refresh! # Explicitly fetch and validate a new snapshot.Login.new(...).call accepts the same keywords. unit_id: selects the unit's
ident, not its portal row ID. Omit it to select the first listed unit.
Returned tokens contain user_id, unit_id and secret sid.
Account authentication and unit-session acquisition are separate stages. Defaults
are timeout: 300, poll_interval: 1, open_timeout: 10, read_timeout: 60, in
seconds. The entire login, including authentication, discovery and polling, must
finish within five minutes; shorter timeout: values are allowed, larger ones
are rejected. Each HTTP operation has a separate 60-second total limit covering
connection, writing and reading, also bounded by the outer login limit. Both use
Faraday's Net::HTTP adapter and standard-library Timeout, without a custom
transport. Server ETA is advisory, not a loop count. Timeout does not establish
that credentials were rejected or the unit is offline.
Ordinary unit requests also have a 60-second total limit, not just a per-read
timeout. Duplex::Request.new(..., timeout: ...) accepts shorter total limits;
open_timeout: and read_timeout: can independently shorten connection/read
waits. The adapter never automatically retries requests.
Snapshot lifetime and temperature semantics
- First reading fetches one complete snapshot; later getters reuse it without
implicit network refresh.
refresh!explicitly replaces it. - Every current-value getter and serializer checks freshness: timestamp must be
newer than
now - 900seconds and no later thannow + 60seconds. Exactly 15 minutes old is expired.valid?inspects cached state without fetching. - Failed refresh invalidates current data and preserves the failure until another
refresh!. A write attempt also discards the pre-write snapshot, even when its response fails; next reading fetches again. No stale fallback is exposed. -
values/as_jsonuse symbol keys;parseduses string keys. Readers includepower/current_power,mode/current_mode,outdoor_temperature,required_temperature,preheat_temperature,input_temperature,preheating/preheating?, andtimestamp. Temperatures are degrees Celsius. -
required_temperatureis the requested temperature. Historicalpreheat_temperaturereader and hash key remain aliases in meaning; both keys are present. This is not a measured preheater temperature. - Optional
input_temperatureisnilwhen unavailable or its discovered logic is unsupported. It is not fabricated as zero. - Legacy
preheatingis an aggregate of heating-related signals, not a verified dedicated preheater state. - Optional
time_zone:accepts an IANA identifier (also onSensorParser.new).nilpreserves process-local timestamp interpretation. Set the actual unit's zone explicitly to remove deployment-zone ambiguity. Invalid zones and ambiguous/nonexistent DST-local timestamps raiseProtocolError. - Device timestamps may omit leading zeroes (for example,
17:7:32). These are normalized while invalid calendar dates and times are still rejected.
Loading the gem registers translations and sets global I18n.default_locale to
:cs. Sensor/mode maps use string keys. user_modes keys are numeric strings,
not input names such as "D1".
Configuration discovery
Unit.new accepts user_ctrl: to reuse a Duplex::UserCtrl for the same unit.
It caches successfully validated layout/text configuration per instance; recreate
it after configuration changes. UserCtrl.data exports JSON-safe configuration,
including input_temperature_source: "rd5_standard" selects the recognized
device source-selection rule; "unsupported" keeps inlet temperature unavailable.
Persist this field alongside the sensor/mode maps and expose it when reconstructing
a custom user_ctrl: object, such as an ActiveRecord model. Without it, only the
legacy direct sensor mapping can be used. Missing/nil metadata retains that legacy
behavior; explicit unknown metadata returns nil, without guessing a sensor.
Custom objects supply name, sensors, modes, user_modes and the persisted
input_temperature_source. Sensor interpretation stays inside the gem, not the
application UI. Command mappings must include discovered power_input, power_switch,
mode_input and mode_switch fields. Derive mappings from the unit's UserCtrl,
not fixture addresses. control.configuration returns the fresh snapshot's
Duplex::RD5Configuration policy ([], fetch, to_h).
Power and mode commands
Setter values must be nonnegative integers, finite integral Floats, or ASCII
decimal-digit strings: 88, 88.0, "88" normalize to 88. nil, booleans,
negative/fractional numbers, NaN/infinity, whitespace, signs and "88.0" raise
ArgumentError. Values are never silently truncated or clamped. Commands also
require a supported configuration and discovered register mapping.
Power semantics follow RD5 H10510 in the vendor's
Communication MODBUS — RD5 and aMotion, version 04,
section 3.1, page 9:
H10510 |
Configuration | Accepted power values |
|---|---|---|
| 0 | Direct speed | 0 or integers 12–100 |
| 1 | Constant flow | Integers 0–100 (configured flow scale) |
| 2 | Constant pressure | 0, 1, 2 (levels) |
| 3 | External input | No power writes; UnsupportedConfiguration
|
| 4 | Multiport | 0, 10–12, 20–22, 30–38 (enumerated settings) |
| Missing/unknown | Unsupported | UnsupportedConfiguration |
These are not universal fan-speed percentages or measured airflow. Modes must be
discovered numeric IDs 0–7 and satisfy equipment prerequisites: 0/2 unrestricted;
1/6/7 require C10508=0; 3 additionally requires C10509=1; 4 additionally
requires H11700=1; 5 requires I11401=1. Missing prerequisites fail explicitly.
Translated current-mode labels are not command values.
Schedule policy uses the discovered control register: manual 0 sends only the setpoint; scheduled 1 or temporary 2 sends the setpoint plus temporary control 2, including for power zero. It does not permanently disable schedules. A temporary request lasts until the next scheduled interval under the documented RD5 policy.
Unconfirmed writes
response = control.set_power(88, verify: false)
response = control.set_mode(2, verify: false)
control.power = 88
control.mode = 2verify: false returns the HTTP response, without application/read-back
confirmation. power= and mode= delegate with verify: false. Ruby assignment
expressions evaluate to their right-hand value, not confirmation. HTTP success
alone does not establish that the unit accepted or applied the request. Writes
are never automatically retried.
Verified writes require an independently proven mapping
set_power(value, verify: true, timeout: 30, poll_interval: 5) and set_mode
default to verification. The default configuration has no proven requested-value
read-back profile: verified calls raise UnsupportedConfiguration before writing.
Neither the PDF's current-value fields nor old fixture idw fields are selected
automatically.
Only supply verification_registers: after independently verifying requested-value
semantics for that exact unit/profile. It accepts a nonempty Hash with symbol keys
:power and/or :mode, and String values matching H plus exactly five digits.
Syntax validation does not establish register semantics. This example deliberately
supplies no literal register address:
# These environment values must come from your independently verified profile.
verified_control = AtreaControl::Duplex::Unit.new(
**tokens,
time_zone: "Europe/Prague",
verification_registers: {
power: ENV.fetch("ATREA_VERIFIED_POWER_REQUEST_REGISTER"),
mode: ENV.fetch("ATREA_VERIFIED_MODE_REQUEST_REGISTER")
}
)
confirmed_power = verified_control.set_power(88, timeout: 30, poll_interval: 5)
confirmed_mode = verified_control.set_mode(2, timeout: 30, poll_interval: 5)Verification fetches a fresh baseline, writes once, then polls for the normalized
request in a snapshot newer than the baseline. One absolute budget includes
baseline, lazy discovery, dispatch, read-back and sleeps. It confirms a requested
setpoint, not physical airflow, effective mode or override of safety functions.
WriteNotConfirmed means outcome unknown after dispatch; do not blindly retry.
Errors and migration
All library errors inherit AtreaControl::Error; invalid caller command inputs
raise standard ArgumentError.
| Error | Meaning |
|---|---|
AuthenticationError |
Portal rejected authentication. |
SessionExpired |
Unit HTTP 401/403, or missing/stale/future snapshot timestamp. Freshness failure alone does not prove authentication expired. |
ProtocolError |
Malformed/unexpected XML, invalid register/timestamp or DST ambiguity. |
TransportError |
Failed HTTP response or connection. |
UnitConnectionTimeout |
Transport timeout or exhausted login/verification-baseline budget; subclass of TransportError. |
UnsupportedConfiguration |
Missing/unsupported configuration, command profile or proven verification mapping. |
WriteNotConfirmed |
Verification budget exhausted after dispatch; outcome unknown. |
Migration from 3.2.x: nil formerly could become zero; it now raises
ArgumentError. Other malformed inputs no longer silently coerce. All cached
getters/serializers can now raise freshness or refresh errors. Handle optional
inlet temperature nil, the additional required_temperature hash key, strict
configuration/mode validation, and preserved manual schedule control. Explicit
set_power/set_mode default to verification; existing assignment setters remain
unconfirmed. These changes require a major-version upgrade from 3.2.x.
Protocol reference and development
See RD5 cloud protocol evidence for supported declarative discovery forms, fixture/PDF differences and current integration blocker. The PDF describes Modbus TCP, not cloud framing, acknowledgements or rate limits. Port 502, enabling Modbus and its five-second batch interval are not prerequisites or established HTTP constraints for this gem.
Run bin/setup to install dependencies. bundle exec rake runs specs then
RuboCop. CI retains the Ruby spec matrix and runs a separate RuboCop job. Focused
test: bundle exec rspec spec/atrea_control/duplex/unit_spec.rb, optionally with
:LINE. WebMock/local fixtures need no portal credentials or physical unit.
Use bin/console for an interactive prompt.
Gem contents come from git ls-files; new runtime files must be tracked before
packaging. bundle exec rake build builds locally. Publishing requires a separate
release decision: bundle exec rake release pushes commits/tags and publishes to
RubyGems; it is not a verification command.
Contributing